IXXAT Smart Grid Gateway With NEW Possibilities

IXXAT (HMS) has offered their Smart Grid Gateways for some time. Click HERE for some blog posts that give you a good overview of the possibilities so far (HERE for HMS or HERE for Beck).
The other day IXXAT has published an extended range of possibilities to share information between many different communication solutions in almost ALL automation applications:

SG-gateway IO
SG-gateway M-Bus Master
SG-gateway EtherNet/IP
SG-gateway PROFIBUS
SG-gateway PROFINET

New:

SG-gateway Media Converter
SG-gateway Switch

All types support as well:

Modbus-RTU master/slave via RS232/485
Modbus-TCP master/slave
DHCP server, SNTP, Network trace (pcap), SNMPv2c
OPC-UA server
MQTT
Codesys network variables

Optional:

IEC 60870-5-104 client/server with redundancy (Norwegian User Convention)
IEC 60871-5-101 master/slave
IEC 61850 client/server (both roles and GOOSE pub/sub are supported simultaneous)
IEC 61850 GOOSE publisher/subscriber
Outstation DNP3
Hardware versions with 3G or 4G modem

Click HERE to visit the IXXAT website for an overview (German).
Click HERE to download a new 12 page pdf bochure (German).

Sunday, October 6, 2019

Next week: IXXAT Smart Grid Gateways at IEC 61850 Global 2019 in London, UK

IXXAT (HMS) will be available at the conference to demonstrate you the latest gateway family supporting IEC 61850, IEC 60870-5-104, Profibus, ProfiNet, Ethernet/IP, M-Bus, ...

IEC 61850 Global 2019
London, UK
Oct 14, 2019, 02:00 AM - Oct 19, 2019, 02:00 AM

Drawing together 150+ IEC 61850 specialists and implementation leaders, this end-user-driven programme focuses on achieving multi-vendor, multi-edition interoperability within the substation and across the wider smart grid.

Click HERE for more details on the event.

New IIoT gateways from HMS allow industrial equipment to communicate with smart grids ...

Click HERE for more details to solve smart grid information models and communications.

Note that the gateway will come with MQTT as well ...

Click HERE for the Gateway with MQTT support.

Wednesday, March 13, 2019

Smart Grid Communication Challenges With IXXAT SG Gateways

Smart Grid communication challenges can easily be solved with IXXAT SG-gateways

New IIoT gateways from HMS allow industrial 
equipment to communicate with smart grids.

IXXAT SG-gateways...
  • Enable easy remote control and management of electrical systems
  • Support IEC 61850 client/server, GOOSE, proxy gateway, IEC 60870-5-104 client/server and VHPready
  • Provide Modbus-TCP client/server and Modbus-RTU master/slave interfaces
  • Enable SNMP, SNTP, and cloud connectivity
  • Provide I/O, M-Bus, PROFIBUS, PROFINET and EtherNet/IP interfaces
  • Are safe – firewall, OpenVPN & password protection
  • Support IEC 60870-5-104 redundancy acc. edition 2 (Norwegian Convention)
Click HERE to enter the world of IEC protocols for power delivery systems
[EN, DE, FR, CN].
Hier klicken ... für ein Kurzvideo und weitere Informationen ... von Martin Matt, Produktmanager Energy Communication bei HMS Networks, über intelligente Smart-Grid-Gateways.

Thursday, July 19, 2018

HMS Networks AB takes over Beck IPC

HMS has taken over the German based company Beck IPC. Beck IPC has a range of products providing IEC 61850, IEC 60870-5, and DNP3 connectivity - I have reported about their products from time to time ... just search for Beck on the blog.

Click HERE for the HMS press release.

HMS (IXXAT) sells some of the Beck com.tom (as Gateways):

Click HERE for Beck com.tom products with above standards implemented.
Click HERE for HMS Gateway products with above standards implemented.

Monday, August 21, 2017

New Application Example for EvaDeHon Package

We have posted a new example extending the use of the Evaluation, Demonstration and Hands-On (EvaDeHon) Package.

We will publish from time to time additional models and documentation for interesting applications. The objective is to help you to understand the various topologies and possibilities to use the IEC 61850 technology for the process information exchange.

One focus is on the application of the IXXAT (HMS) Smart Grid Gateways.

The example offers polling and reporting (Server on PC, Client on IXXAT WEB-PLC Gateway). The download contains the client CID for the gateway, the server CID and the JSON file for the PC. The gateway polls every 2 seconds and receives reports every 5 seconds - these intervals can be configured. Additionally it includes some specific documentation.



Click HERE for more information.

Monday, July 3, 2017

An All NEW Evaluation, Demo, Hands-On Package for IEC 61850 and IEC 61400-25

NettedAutomation GmbH (Karlsruhe, Germany) has released an All NEW Evaluation, Demo, Hands-On Package for IEC 61850 and IEC 61400-25 (EvaDeHon) for immediate download and use!
The new EvaDeHon Package comprises the roles Client, Server, Publisher, and Subscriber running on a PC, HMS (IXXAT, Beck IPC) Gateways, SystemCorp IEDs, ...
The new solutions allow to run multiple IED models (all roles) in parallel on one PC (simulating IEDs of a complete system!) ... and more. The roles and applications are configured directly by SCL files (.cid). You can build your own models and run them with all roles ... if configured.
This Package is based on our 30+ years of experience. We are really proud of offering these tools to the industry today! Sit down, enjoy and relax ...


Copyright, 2017, Michael Hüter

Click HERE to download the documentation only [pdf, 3.2 MB]
Click HERE for downloading the demo package including the documentation and license conditions.

Example: Server and Client on two PCs:


Many topologies on PCs:


... and topologies with gateways:


Click HERE to download the documentation only [pdf, 3.2 MB]
Click HERE for downloading the demo package including the documentation and license conditions.


Wednesday, April 26, 2017

NEW IEC 61850 Demo Package for Windows available

The main purpose of the new demonstration and evaluation package is to provide a free of charge simple and easy to use IEC 61850 Client/Subscriber Tool (running on Windows PCs) that can be used to communicate with a Server/Publisher implemented on the platforms:

Beck IPC DK151 Development Kit for SC145 (DK61)
Beck IPC com.tom / IXXAT SG-gateways (WEB-PLC)
SystemCorp Smart Grid Controllers
Windows PC

Several other uses cases are possible:

The demonstration uses a single generic SCL model (and a derived JSON file [JavaScript Object Notation] that can (beyond the main purpose) be used on the above platforms to automatically configure (tree structured graphical applications) for Clients, Server/Publisher, and Client/Subscriber roles as shown on the next slides.

The specification of additional models (.icd and .json) could be provided for a fee. 
Contact NettedAutomation if you are looking for other models, please.
Click HERE for further details and instructions to download the new package including the documentation.
Click HERE for documentation only.
The package is used in our training courses.

Sunday, April 23, 2017

Final Call for IEC 61850 Training Courses in May 2017 in Karlsruhe (Germany)

The following two training courses are just one (two) weeks away:

02.-05. May 2017, Karlsruhe/Germany:


Click HERE for details - and register as soon as possible.

09.-12. Mai 2017, Karlsruhe/Deutschland
HIER klicken - für Details zum Training in Deutsch

Thursday, April 13, 2017

HMS Smart Grid Gateways Are Now IXXAT SG Gateways

The HMS Smart Grid Gateways (supporting a wide range of standards like IEC 60870-5-104, IEC 61850, Modbus TCp/IP, ...) are now marketed by HMS under the HMS brand IXXAT Energy SG Gateways.
IXXAT SG-gateways... 

  • enable easy remote control and management of electrical systems
  • allow to log and display application data and energy consumption
  • provide IEC61850 client/server (publisher/subscriber) and IEC60870-5-104 client/server support
  • have in-built Modbus TCP client and Modbus RTU Master interfaces
  • provide connectivity for I/O, M-Bus, PROFIBUS, PROFINET and EtherNet/IP based devices

Click HERE for more details [EN]
Click HERE for more details [DE]

Thursday, February 16, 2017

IEC-61850-Seminare in Deutsch (Mai und Dezember 2017)

NettedAutomation GmbH bietet in 2017 zwei IEC-61850-Seminare zu unschlagbaren Preisen in Karlsruhe an:

09.-12. Mai 2017 
05.-08. Dezember 2017

Die drei (3) Blöcke (1 Tag + 2 Tage + 1 Tag) können einzeln oder in Kombination gebucht werden. Sie entscheiden selbst, ob Sie nur einen Tag von Ihrem Arbeitsplatz fern bleiben möchten oder zwei, drei oder vier. Je nachdem, wieviel Zeit Sie investieren wollen oder können und welchen Bedarf Sie haben.

Lernen Sie, wie über 4.000 Teilnehmer vor Ihnen, was IEC 61850 und andere Normen wie IEC 60870-5-10x oder IEC 62351 (Security) bedeuten. Gewinnen Sie einen Einblick in relevante Realisierungen wie die FNN-Steuerbox oder VHPready, die auf IEC 61850 aufbauen. Verstehen Sie, wie Feldbusse über lostengünstige Gateways in die Anlagen eingebunden werden können.

HIER klicken, um zur Beschreibung und den Anmeldeunterlagen zu gelangen [pdf, 430 KB].

Beachten Sie auch, dass die meisten Seminare als Inhouse-Kurse stattfinden! Falls Sie Interesse an einem Inhouse-Kurs (in deutsch, englisch, italienisch oder schwedisch) haben sollten kontaktieren Sie uns bitte!

Friday, October 7, 2016

Huge KIT Energy Lab 2.0 - Relies on IEC 61850

The KIT (Karlsruher Institut für Technologie) in my hometown Karlsruhe/Germany is deeply involved in several projects related to the Energiewende. One of the crucial components is the "Energy Lab 2.0".

In "A Concept for the Control, Monitoring and Visualization Center in Energy Lab 2.0" the authors Clemens Düpmeier, Veit Hagenmeyer, Ralf Mikut, and Karl-Uwe Stucky present an interesting concept.

Click HERE for a 16 page presentation presented in November 2015.

The research focuses on the APPLICATION of Control, Monitoring, and Visualization of various aspects of energy systems (gas, electricity, heat) - not just electrical systems.

IEC 61850 is THE solution for the process instrumentation - share process information in a standardized way.

These people have understood that the focus is on applications rather than on protocols ...
The 14 Layer Cake I had after a nice dinner in Jakarta shows that the automation of the energy systems of the future is more than "just another protocol" ... applications based on standard protocols are the crucial aspects:



Hm, the cake was very delicious.

Tuesday, August 16, 2016

IEC 61850: Gateway for Cloud Computing and Fog Computing

Cloud computing and Fog Computing is in principle supported by a single gateway offered by HMS:

  • Bridges any signal from the process level directly to your own or third party cloud.
  • Maps any signal from Modbus, Profibus, ProfiNet, Ethernet/IP, IEC 61850, IEC 61400-25, IEC 60870-5-104 ... to Modbus, Profibus, ProfiNet, Ethernet/IP, IEC 61850, IEC 61400-25, IEC 60870-5-104 ...
  • Provides many logic functions AND, OR, Timer, Counter, ... to build applications.
  • Has digital Input and Output pins.
  • Reads M-Bus.
  • Supports Client, Server, Client/Server, Client/GOOSE-Subscription (with or more Server/GOOSE-Publishers), and Sever/GOOSE-Subscription
  • What else do you need for simple applications?

Click HERE for more information.

Saturday, August 6, 2016

IEC 61850-90-10 Draft Technical Report on Schedules just published

IEC TC 57 just published the Draft Technical Report:
IEC/TR 61850-90-10 Ed.1.0 (57/1762/DTR)
Communication networks and systems for power utility automation -
Part 90-10: IEC 61850 objects for scheduling

Closing date for voting is 2016-09-30

Schedules establish which behavior (e.g., tariff 1 or 2, mode 1 or 3) or expectation (e.g., forecast) is applied during specified time periods. A schedule consists of a series of entries with a setting for the value of a setpoint, the selection of a particular mode or the value of a parameter for a mode.
There are different ways to operate a scheduled entity based on the following operation principles:

  • The actual values of a scheduled entity (e.g. active and reactive power produced or consumed) are directly controlled using setpoints and controls. For example, the DER system reacts on changes of the setpoints or on controls (e.g. start or stop the DER system) in real time.
  • The functional behavior of a scheduled entity is configured to operate in a mode in which it responds to locally sensed conditions (e.g. Volt-VAr Mode in case of DER) or externally provided information (e.g. prices). 

The schedules offer a very powerful functionality that can be used in many different applications.
Currently we have two major applications in Germany  that make use of the schedules: 
  1. VHPready
  2. FNN Steuerbox
NettedAutomation has implemented the most crucial concepts on an embedded controller used in the HMS gateways.

More to come soon.

Sunday, July 31, 2016

Power Quality Meter Goes IEC 61850 and IEC 60870-5-104

Friday last week I was involved in installing a high level Power Quality Meter (UMG 512 from Janitza) to monitor the power for a new building:



The objective was to apply a smart gateway between the Meter and IEC 61850 and IEC 60870-5-104. It took some 90 minutes to install the meter and configure it for Modbus TCP communication. The gateway used is an HMS Anybus SG Gateway I/O.



The gateway offers connectivity to Profibus, ProfiNet, Ethernet/IP, and other protocols.
The gateway reads out 22 signals from the Meter (all new Meters from Janitza use the same addresses for the basic signals):


The Modbus signals (from an UMG 604) are listed in the gateway for polling:



As well we need to configure the Signals for IEC 61850 and IEC 60870-5-104:


The signals in IEC 61850 are configured with an SCL File. The 104 signals need manually configuration.











Finally we need to program the mapping from Modbus to IEC 61850 LNs and IEC 60870-5-104 signals. The drop-down menu is used to place the signals to the screen:



Finally the inputs are linked to the outputs:



The signals from the Meter are automatically exposed through IEC 61850 and IEC 60870-5-104 servers.
The IEDScout 4.1 from Omicron is used to connect to the IEC 61850 Server in the Gateway:



And the QTester104 receives messages from the IEC 60870-5-104 server:



Lesson learned: It took less than one hour to configure the Gateway and use it.
This is likely the easiest and fastest way to communicate Power Quality Meter signals through IEC 61850 and IEC 60870-5-104. 

Tuesday, June 28, 2016

VHPready - Offener Industriestandard auf dem Vormarsch

Die Versorgungssicherheit in der Energiewende soll durch innovative Applikationen wie Lastmanagement und virtuelle Kraftwerke gewährleistet werden. Ihre Aufgabe ist es, die natürlichen Schwankungen der erneuerbaren Energien auszugleichen. Der offene Industriestandard VHPready fördert dabei auch die Einbindung industrieller Anlagen und Lasten in die Leitwarte und die notwendige Kommunikation (Profibus, ProfiNet, Ethernet/IP, Modbus, ...). Für den Informationsaustausch werden die beiden Lösungen angeboten: IEC 60870-5-104 (klassische Fernwirktechnik) und IEC 61850-7-420 (moderne Informationsmodelle und Austauschmechanismen).
Im SPS-Magazin finden Sie einen aktuellen Artikel von HMS.
HIER klicken, um den Artikel zu lesen.

Eine kostenlose Evaluierungssoftware unter Windows ist verfügbar (C#-Anwendung unter Verwendung des SystemCorp IEC 61850 Stack/API; Server und Client; C#-Anwendung mit Sourcecode).
HIER klicken, um zum Download zu gelangen.

Client-Anwendung (links) und Server-Anwendung (rechts) unter Localhost (auch mittels SCL-File konfigurierbar für PC-PC-Kommunikation mit Nachrichten auf TCP/IP):



Die HMS-Gateways unterstützen sowohl Server- als auch Client-Rollen (für IEC 60870-5-104 als auch für IEC 61850.

Saturday, April 9, 2016

The Complete Content of the IEC 61850 News Blog is now Available as Single PDF Document

For those readers of this IEC 61850, IEC 60870-5/6, DNP3, … news blog that want to get the complete content as a single pdf document, it is just a click away … it contains 1120+ posts from 2008 until 2016-04-09. Once you have downloaded the file you can easily browse the content … search … mark … copy … You will find useful information about the standards, vendors like ABB, HMS, Siemens, or utilities …

Click HERE to download all posts of the IEC 61850 blog in a single pdf [14 MB, 823 pages DIN A4]

Enjoy!

In case you have a question, drop us an EMAIL.

Tuesday, February 2, 2016

HMS Updated their Web Pages for IEC 61850, IEC 60870-5-104, ... Anybus SG-gateways

The Anybus® SG-gateway™ family is designed to specifically target Demand Response (networking of industrial electric loads) and Virtual Power Plants (networking of energy resources like biogas plants or combined heat and power units) applications.

Remote Terminal Unit
The SG-gateways support the communication protocols used in the energy sector, e.g. IEC 60870-5-104, DNP3 and IEC 61850; as well as protocols supported by the electric equipment in the field, e.g. Modbus or M-Bus. In addition, thanks to the built-in Anybus CompactCom interface, they can also communicate with fieldbus or industrial Ethernet networks such as Profibus, Profinet, EtherNet/IP or any other industrial network.



The new Web pages provide all information needed to build a information infrastructure for Smart Grid for a smarter power network for the future.

Click HERE to visit the Anybus Web site.
Click HERE for a great news post at the Anybus Web site.

HMS will demonstrate VHPready products during the E-World Exhibition.
Click HERE for more information.

Saturday, January 2, 2016

Started the Year 2016 successfully with the Omicron IEDScout 4.10

I hope you had a good start into the year 2016!

During the last days of 2015 and the first days of 2016 I have set up a new notebook and upgraded to Windows 10, Office 2013, ... and Omicron's IEDScout 4.10.

I had to test a control model with operate services. The version 3.0 was very confusing in getting me the information I was looking for. So I decided to upgrade immediately to version 4.10.

This was one of the best decisions of the "young" year 2016!

The version 4.10 is way easier and less confusing to be used for testing real products! The model shows exactly what is crucial for the tester:


This version is an IEC 61850 tool - not just a MMS browser with some flavor of IEC 61850.

Here is the link to the page for free downloading of the fully functional demo version:

https://www.omicronenergy.com/en/products/all/secondary-testing-calibration/iedscout/noc/1/#Description

If you are looking for a professional IEC 61850 Browser and testing tool: The IEDScout is exactly what should test and consider to purchase.

So, the second day of 2016 was already a successful day here in my office. More to come.

I look forward to helping you to get the right education and tools.

Thursday, November 26, 2015

IEC 61850 DLL Demo with Looging and Log-File

The DLL Demo based on SystemCorp’s IEC 61850 Stack/API can very easily be configured with the corresponding CID-File for the Server to log data attributes listed in a DataSet. The log entries are stored in an XML file.

All you need to do is: Add the following 3 lines in the configuration file (after line 52):

Directory: /Resources_localhost (/Resources_2machines)
File: /VHPServer_localhost.icd (/VHPServer_2machines.icd)

image

<LogControl datSet="BHKW_ST1" intgPd="0" logEna="true" logName="DLLDemo" name="DLLTestLog">
    <TrgOps dchg="true"/>
</LogControl>

Restart the Serer and you have a log that is filled with events coming through the DataSet "BHKW_ST1".

Model as seen by an IEC 61850 Client (Browser):

image

The file format (DLLDemo.Xml) is vendor-specific:

image

Two Log Entries (4 and 5):

image

Note: The time stamp “t” is “000…0” because the Server application program is not providing it to the Stack … this could be done by extending the C# application source code that comes with the Demo package … if you are familiar with C# programming.

The services QueryLogByTime and QueryLogAfter will be available in the future.

The Log Model is available in the SystemCorp Library. It means, e.g., it is available in devices like the HMS SG line. The log file may grow very fast … be careful not to consume all memory resources. In the future the file will represent a circular buffer so that it will never overflow (by overwriting the oldest entries – as defined in IEC 61850-7-2).

There is a possibility to convert the XML coded Log file into another XML based file: COMFEDE („Common Format for Event Data Exchange") published by IEEE.

Click HERE for Information on COMFEDE (DE).
Click HERE for Information on COMFEDE (EN).

Click HERE if you are interested to download the DLL Demo.

Tuesday, November 24, 2015

HMS offers also Gateways from Profibus and EtherNet/IP to IEC 61850 an IEC 60870-5-104

The Anybus SG-gateway family is designed for use with Smart Grid applications such as, control of electrical equipment, metering applications and with the bridging of Industrial Networks with the Power Grid.

The Anybus SG-gateways were originally developed under the HMS's Labs Initiative, known as "Labline". Now that the gateways have been finalized they are currently under the transition of moving under the "Anybus" brand name. The product remains unchanged - just labels and product color and web interface are in the process of update. Until Jan 2016 they are available as the "Labline" brand.

The SG-gateways support IEC61850 client/server, IEC60870-5-104 client/server and Modbus TCP client/server & RTU master/slave protocol stacks. Additional industrial automation standards like Profinet, Profibus, EtherNet/IP or metering protocols like M-Bus are also available in some models. 

image

Click HERE for more details.