Thursday, July 17, 2014

IEC 61850 (MMS) running over LTE

Giang T. Pham did some research on running IEC 61850 (MMS) over LTE. The result is a Master Thesis at the University of Twente:

“Integration of IEC 61850 MMS and LTE to support smart metering communications”

“… The objective of this research is to integrate IEC 61850 MMS and LTE to support communications between smart meters and the central meter data management system. The research includes a literature study of IEC 61850 MMS protocol, focusing on its requirements to support smart metering communication, and simulation-based performance evaluation of IEC 61850 MMS smart metering traffic over LTE network. …

… Since both MMS and LTE support the use of TCP/IP communication profile, the mapping of MMS over LTE to support remote control communication is feasible … the simulation results prove that the integration of IEC 61850 MMS and LTE is not only possible but also provides good performance in term of delay, throughput and packet loss.

Click HERE to download the Master Thesis [pdf].

Why does Security often have a low priority?

During a conversation with a manager of a vendor of Energy Management Systems (EMS) today, I was surprised hearing that they offered a training course on Security measures in 2013 – but had to cancel the course because of too less registrations! Could that be true in 2013?

Here is some information on security measures easy to read and understand – maybe hard to implement:

Whitepaper
Anforderungen an sichere Steuerungs- und Telekommunikationssysteme

White Paper
Requirements for Secure Control and Telecommunication Systems

Click HERE for the bilingual document [pdf]

There is also a companion document (in German) available that gives further guidelines on how to apply the requirements for control center level systems, for communication infrastructure level, and for substations and RTUs:

“Anforderungen an sichere Steuerungs- und Telekommunkationssysteme
Ausführungshinweise zur Anwendung des BDEW Whitepaper”

These requirements are mandatory for vendors!!

Click HERE for the document [pdf, DE].

Every expert in the energy automation business should read, understand, and apply these requirements.

On page 58 you can read (in German):

“Entsprechend den technischen Möglichkeiten sollten in allen Bereichen standardisierte IEC-Protokolle angewendet werden. Der private Bereich dieser Kommunikationsprotokolle sollte nach Möglichkeit nicht verwendet werden.
Eine Verschlüsselung der Protokolle nach IEC 62351 sollte durch den Betreiber geprüft werden, wobei ggf. auftretende Einschränkungen bei der Fehlerdiagnose sowie die notwendige Infrastruktur und Prozesse zur Schlüsselverwaltung berücksichtigt werden sollten.
Dort, wo aktuelle Systeme und Geräte noch nicht die Möglichkeit der Verschlüsselung nach IEC 62351 bieten, sollte die Fernwirkübertragung daher auf den unterlagerten Netzwerkebenen geschützt werden, z.B. durch Nutzung von VPN-Technologie oder SSL/TLS-Tunnelung.
Insbesondere für IP-basierte Protokolle sollten entsprechend sichere Netzwerkstrukturen vorgesehen werden (siehe 2.3).”

By the way, the whitepaper can be used by English speaking experts to learn German – and vice versa ;-)

Wednesday, July 16, 2014

infoteam software supports IEC 61850

Programming application software using OpenPCS (infoteam implementation of IEC 61131-3) is one of the well known options in the PLC world. OpenPCS also incorporates IEC 61850 client/server and publisher/subscriber roles as well as SCL configuration. The result is, for example, a powerful “Smart Grid Controller”:

Software for IEC 61850

Click HERE for more information [EN].
Click HERE for more information [DE].

Tuesday, July 15, 2014

Security – A never ending Story

The more our societies rely on computerized information sharing the more we need to take care that we implement protection mechanisms to run the systems reliable. There are many discussions and approaches how to make or keep the systems robust.

These days there are several discussions going on about whether it is better to keep the vulnerabilities top secret or to let people know how close we are to a lot of critical damages.

Whatever your position is: There is a need to increase the efforts to keep control over our critical infrastructures. And this will require a lot more resources than those written in many business plans for 2014, 2015 and beyond. We have to pay for it anyway: NOW or LATER! Maybe it will be more expensive to pay later!

It is not sufficient to know the issues – We must prevent or fix them actively … as soon as possible.

The other day a new study on ICS and SCADA Security was published:

Critical Infrastructure: Security Preparedness and Maturity

Sponsored by Unisys Independently conducted by Ponemon Institute LLC

“The purpose of this research is to learn how utility, oil and gas, alternate energy and manufacturing organizations are addressing cyber security threats. These industries have become a high profile target for security exploits. Moreover, it has been reported that if their industrial controls systems (ICS) and supervisory control and data acquisition (SCADA) systems were attacked the damage could be enormous. …
As the findings reveal, organizations are not as prepared as they should be to deal with the sophistication and frequency of a cyber threat or the negligence of an employee or third party. In fact, the majority of participants in this study do not believe their companies’ IT security programs are “mature
.””

Click HERE to download the report.

My personal understanding is: Everything that is remotely accessible can be breached; everything that is programmed can be re-programmed.

Isn’t it true what King Salmon wrote in Ecclesiastes 1,18 (King James Version): “For in much wisdom is much grief: and he that increaseth knowledge increaseth sorrow.”

This is our daily experience! Or?

Friday, July 11, 2014

New Power Quality and Energy Measurement device supporting IEC 61850

Bender Grünberg offers a new Power Quality and Energy Measurement device supporting IEC 61850 information exchange:

The digital universal measuring device PEM735 is suited for measuring and displaying electrical quantities of electricity networks. The device measures currents and voltages, energy consumption and power, and displays the individual current/voltage harmonics for assessment of the power quality in accordance with DIN EN 50160. The accuracy of active energy measurements corresponds to class 0.2 S in accordance with DIN EN 62053-22 (VDE 0418 part 3-22). The current inputs are connected via external …/1 A or …/5 A measuring current transformers.

Click HERE for general information.
Click HERE for the data sheet.

Wednesday, July 9, 2014

Deutsche Gasversorgung nutzt Profil für IEC 60870-6 TASE.2

20 Jahre nach der Veröffentlichung der Normenreihe IEC 60870-6 TASE.2 (ICCP) ist das Thema TASE.2 bei der deutschen Gasversorgung immer noch hochaktuell! Das wird sicher auch für die nächsten 20 und mehr Jahre so sein!

IEC 60870-6 TASE.2 basiert auf derselben Basistechnologie wie IEC 61850 und IEC 61400-25: MMS (Manufacturing Message Specification, ISO 9506). MMS ist aus dem MAP-Projekt Mitte der 80er Jahre hervorgegangen.

Der DVGW-Arbeitskreis „Standardisierung des Informationsaustausches zwischen Dispatchingzentralen“ empfiehlt für den Austausch von Prozessdaten den Einsatz des „Telecontrol Application Service Element Two“ (kurz TASE.2).

Die Spezifikation des TASE.2-Standards zum Einsatz zum Prozessdatenaustausch zwischen Leitzentralen der Gaswirtschaft sowie einen Leitfaden zur Anwendung finden Sie in der DVGW Gas-Information Nr. 18 "Prozessdatenaustausch zwischen Leitzentralen der Gaswirtschaft auf Basis von TASE.2" , Ausgabe Februar 2012.

Der Leitfaden gibt einen Überblick über die wichtigsten Merkmale und Funktionalitäten von TASE.2 und die konkrete Anwendung von TASE.2 im Extranet der Gaswirtschaft. Der Leitfaden kann auch als Profil verstanden werden. Von der Vielzahl der Möglichkeiten der TASE.2 werden die Definitionen ausgewählt, die für den Anwendungsbereich zu verwenden sind – um einen hohen Grad an Interoperabilität zu erreichen.

Hier klicken, um die DVGW Gas-Information Nr 18 herunterzuladen [pdf, nur lesbar]. Eine druckbare Pdf-Version kann erworben werden.

Vor 15 Jahren haben die an der Normung beteiligten Experten den folgenden Report veröffentlicht:

etz-Report 32
Open communication plattforms for telecontrol applications:
benefits from the new standard IEC 60870-6 TASE.2 (ICCP)

Einige Exemplare des etz-Reports 32 stehen noch zur Verfügung und werden kostenlos abgegeben.

Die hier beschriebene Profil-Bildung sollte auch für IEC 61850 in anderen Anwendungsbereichen zum Vorbild dienen! Dafür werde ich mich verstärkt einsetzen.

Monday, July 7, 2014

Industrieforum VHPready nimmt Fahrt auf

Das “Industrieforum VHPready” erarbeitet einen Standard für virtuelle Kraftwerke, der auf den Normen IEC 60870-5-104 und IEC 61850 aufbaut.
Mittlerweile haben die ersten Arbeitsgruppen des Vereins ihre Arbeit aufgenommen:

AG 1: Weiterentwicklung von VHPready
AG 2: Zertifizierung/Präqualifikation
AG 3: Marketing, Internationalisierung und Standardisierung

Vision und Mission des Vereins:

Das Industrieforum VHPready e.V. setzt sich für die Realisierung der Energiewende durch die standardisierte Vernetzung dezentraler Energieanlagen ein. Der Standard VHPready und seine Zertifizierung gewährleisten das nahtlose, sichere und wirtschaftliche Zusammenwirken aller steuerbaren Komponenten und deren Kompatibilität. VHPready bildet die Grundlage für den flexiblen Zusammenschluss
dezentraler Energieanlagen zu virtuellen Kraftwerken.

Hier für den Flyer klicken.
Hier finden Sie den Zugang zu VHPReady.
Hier ist eine aktuelle Veröffentlichung in den EW Medien.

Mitte Juni 2014 waren folgende Firmen und Organisationen Mitglied: 2G Energy • 50Hertz • Beck IPC • Bosch SI • Energy2market • E.ON Connecting Energies • IABG • Fraunhofer Gesellschaft • IT&I • LichtBlick • Optimax Energy • Phoenix Contact • SSV Software Systems • Vattenfall Europe Wärme • WAGO Kontakttechnik • Younicos

Das Industrieforum ist aus meiner Sicht die erste ernstzunehmende Aktivität in Deutschland, die Vielfalt in der Kommunikation zwischen den vielen dezentralen Energieerzeugungsanlagen (Energie-Erntemaschinen) und Leitsystemen zu reduzieren beziehungsweise erst gar nicht aufkommen zu lassen.

Ohne (eine oder vielleicht zwei) einheitliche Kommunikationslösungen werden die Aufwendungen bei der Realisierung von notwendigen Informationsaustauschverfahren sehr hoch – was dazu führt, dass entweder viele Energieerzeugungsanlagen gar nicht oder nicht optimal eingesetzt werden können oder die Anlagen nur mit einer einzigen Leitstelle kommunizieren kann.

Die Mitarbeit im Industrieforum VHPReady sollte ein Muss für alle Netzbetreiber, Betreiber von virtuellen Kraftwerken und von dezentralen Erzeugungsanlagen sein!

Sunday, June 29, 2014

One Standard – multiple Terms for the same Thing

The Standard series IEC 61850 and IEC 61400-25 define hundreds of new terms for information models and communication models. Usually a term defined in one part and re-used in another part is the same (syntactically and semantically). In some cases you will find different terms for the same “meaning”.

Here is one example to explain what I mean:

The Standard part IEC 61850-7-2 (ACSI) defines in clause 12.3.3.3:

TrgOp [0..2] – trigger option

The attribute TrgOp of type TriggerConditions shall define the trigger conditions (associated to a data attribute of a data object) that may cause a report to be sent or a log entry to be stored into a log.

Three values are defined to be used inside the data object:

dchg data-change A report or a log entry shall be generated due to a change of the value of the associated data attribute

qchg quality-change A report or a log entry shall be generated due to a change of the value of the associated quality data attribute q

dupd data value update A report or a log entry shall be generated due to updating the value of a data attribute. An updated value may have the same value as the old
value. An example is freezing the value of a freezable data attribute updating the value of another data attribute, which could lead to the same value it already has.

The trigger conditions integrity and general-interrogation of the TriggerConditions type are used independent of instances of a data object.

The service parameter IntegrityPeriod is mapped to intgPd:

17.2.2.12 IntgPd – integrity period

IntgPd shall indicate the period in milliseconds used for generating an integrity report.

So far so good – even we have already three terms:

integrity, IntegrityPeriod, IntgPd, or integrity period.

What does part 6 (SCL) define?

<xs:complexType name="tTrgOps">
   …
   <xs:attribute name="period" type="xs:boolean" use="optional" default="false"/>

and for the value attribute of “period”: intgPd="2000" in the report configuration element.

So, we find six terms that mean more or less the same thing … you have to understand what they mean and when to use one or the other!

When it comes to IED Configuration Tools (ICT), you may have to learn new terms again:

image

Here the SCL attribute “period” is set to true, if the checkbox for “Included in Integrity/Poll” is set.

By the way, these terms describe something quite easy: Push all (!) values of a DataSet every n milliseconds. Without a request from the client. In addition to the cyclic push you may configure the server to report the value of a single signal after it has changed (data change)):

image

You want to learn how to use the standard? We offer training courses that help you to apply the standards in your daily business! It is more convenient to attend a training than to read all the standards … we have the long-term experience that we would like to share with you.

Friday, June 27, 2014

Version 2 of SystemCorp’s IEC 61850 Stack and API available

The V2.02 of SystemCORP's IEC 61850 library is now available for all platforms. A new demo and evaluation package that runs under Windows is also available. This evaluation provides the DLL (includes Stack, internal IED SCL configuration tool, and API), a server application, and a client application. The demo applications come also with source code in C/C++:

image

This version supports both Edition 1 and Edition 2 of the IEC 61850 standard, and includes multiple improvements to system communication and memory management.

The following list shows the communication service models implemented:

image

and these are the API functions:

image

The API is very convenient and simple!

Click HERE for more general details.
Click HERE for the getting started check list …

We are offering 6 hours comprehensive hands-on training in our standard public training courses like the one scheduled for October 15-17, 2014:

http://nettedautomation.com/seminars/uca/sem.html#fra14-05 

The most efficient education are offered as in-house training courses.

Tuesday, June 10, 2014

Useful Links for Visitors of the SG Paris 2014 - From Smart Grids to Smart Networks, June 11-13

In order to save paper copies, please find links to some interesting documents I usually distribute during conferences and exhibitions:

"The Beautiful Simplicity of the Integration of Modbus, DNP3, IEC 60870-5-104, and IEC 61850 into a powerful WEB-PLC operating on an Embedded Controller"
com-tom-Gateway_Introduction_2014-03-21.pdf

com.tom WEB-PLC and Integration of IEC 61850 and IEC 60870-5-104 - This document explains the first steps
com.tom_WEB-PLC_61850-104_GettingStarted_V01.pdf

"Easy, Affordable and Fast Integration of IEC 61850 in Small Devices". - More about IEC 61850 on IPC@CHIP®.
IEC61850_Schwarz_EN_2014-03-21.pdf

Personal experience, capabilities, of Karlheinz Schwarz ... introduction on IEC 61850, training modules, feedback from attendees, list of companies, countries, and pictures

Training opportunity 15-17 October 2014 in Frankfurt/Main, Germany

Friday, June 6, 2014

A REFRESHER ON THE “STANDARDS CONTINUUM”

Erich Gunther, Aaron Snyder and Grant Gilchrist, EnerNex have published an interesting article in the SGIP Newsletter, Volume 6, June 2014 Issue:

A REFRESHER ON THE “STANDARDS CONTINUUM”

Their Conclusion is right:

“Often misapplied, the term “standard” is truly only applicable in certain situations. The author of this piece advocates reserving the use of “standard” for de jure standards, especially when employed without the "de jure" modifier. There may appear to be little harm in referring to de facto "standards" simply as “standards,” but this actually dilutes and confuses the definition in the manner that the term "engineer" is often misapplied to functions requiring no engineering education or certification. For example, in these cases, it is preferable to use the applicable term of "specification," "requirements" and "requirements specification" instead of "standard."”

Click HERE for the full article.

So far so good. There are other languages that differentiate between “Standard” and “Norm”, like in German. German “DIN Standards” are specifications that are reflecting a document that has been published with lower hurdles than a “Norm”. The “DIN Norm” compares to the de-jure Standard.

The reality is more complex than just to differentiate between de-jure Standards and other documents. The (de-jure) Standards have to be extended in many cases by non-de-jure Standards: e.g., Implementation agreements that can be written by a Two-party (two vendors, one vendor and one user, one vendor and one testlab, …), an Alliance, Users Group, or standardization bodies.

The future power delivery systems will need many combinations of de-jure (Base) Standards and non-de-jure Documents (Implementation agreements, Profiles, … and even Green-Tissues-List as in case of IEC 61850, IEC 61400-25 – these are documents that are refer to de-jure Standards).

In the end of the day, we want to get interoperable devices to build multi-vendor automation systems for the future power delivery system! Or?

In case of IEC 61850 I see a lot of pressure to come up with more “official” Implementation agreements or Profiles that are agreed by more than two parties, two companies, or two experts.

One good example is the VHPReady Industrieforum.
Click HERE for the current Specification 3.0 in English.

This is a good starting point – it’s not yet the final result … to expected early 2015.

Wednesday, June 4, 2014

MegaWatt Needs Smarter Megabit/s

What do we need? Huge countries need many MWatt (unit of power) to survive. To get the power whenever we want to use it, we need more “Smart Mbit/s” (“smart” data transfer rate in Mega bit per second). That means: more communicating devices … maybe tens of Millions in some time down the road. What do 1,000 MegaWatt (= 1 GW) and 1,000 Mbit/s (= 1 Gbit/s) have in common? These are huge numbers! And more: We need them both in the near future! The crucial issue is here: One needs the other. Zero GW means Zero Gbit/s and Zero Gbit/s means Zero GW.

Yes, you got it! The two are becoming increasingly interdependent!

There is (mainly) ONE medium to carry power: wires. There are hundreds or even thousands of media to communicate information! Guess you could not count them all. In order to keep the cost for the future power delivery system reasonably low, we could and should think of preventing the proliferation of communication systems. Guess you agree. But: Which solutions are worth to use? No doubt: IEC 61850, IEC 60870-5-104, DNP3, Modbus, … are those that would do a good job!

I would be very happy to have as many communication systems as we have power delivery systems: DC 24V, DC 48V, 3 phase AC 110V/60Hz, 3 phase AC 240V/50 Hz, … and a few more.

Clark Gellings (one of the world’s leading experts on the electricity system, ERPI Palo Alto) talked in a podcast about “The Future of the Power Grid”. He talks about crucial aspects of the future power systems. Key issues (from my point of view) are summarized in the following three points:

Question:
“So what are a few of the things that will have to happen between now and 50 years from now to make your vision of the grid a reality?

Clark Gellings’ answer:
Well, first, we’re going to need communications standards that allow devices to talk to one another, so that we don’t have the problem we have now. For example, in buildings, the electronics that are being used have as many as 28 different communications architectures. And so one building technology that might control some new thermal storage unit you have may not be able to talk to another device in that building.

Number two, the computer system that would control these millions of nodes in any given region of the United States, they don’t exist. I mean, we can control tens of thousands of nodes, and we do now, but we’re going to need to control millions of nodes. So that’s another area of development.

And thirdly, technology. For example, power electronics to fully be able to control, in a very fluid way, the power systems, even to the point of doing things like having the system self-heal, or taking action so as to mitigate from an outage that it sees, even before necessarily the outage has occurred.”

… sounds very expensive!? Not that much … listen to Clark Gellings.

Click HERE to listen to the podcast, find a link to download the mp3, and read the content.

Anyway, the 28 different communication architectures in the building automation he mentions are not so bad - compared to the factory automation with hundreds of solutions!

image

why not use the IEC 61158 (solutions)? Because it has too many!

image

IEC 61850 is about to unify most of them (at least at the near-process level where we find the Millions of signals to be shared between Millions of smart devices). And to provide smarter mechanisms to share information.

I hope we can convert more Mbit/s into “Smart Mbit/s”: using them in a smart way. Using smart communication mechanisms (like IEC 61850) will require less bandwidth and smart power systems will need less MW.

Friday, May 30, 2014

Exhibition in Paris: SG Paris 2014 - From Smart Grids to Smart Networks, June 11-13

You are invited to stop at booth i4 at the SG Paris 2014 - From Smart Grids to Smart Networks, and see IEC 61850, IEC 60870-5-104 and Gateways in action:

com.tom -Smart Grid solution

The Exhibition & Conference start from June 11 to 13 in La Défense (Paris) – daily from 8:30h – 19:00h).

In France, Smart Grid technologies have been rapidly developing over the course of the past few years, with high stakes surrounding the roll-out of smart meters, and notably ERDF's highly publicized meter, Linky, and GRDF's Gazpar.

The Smart Grids Paris trade show is now one of Europe's leading events in the Smart Grids field, counting 3000 attendees, 70 exhibitors and almost 150 speakers.

Beck IPC, EBDS and NettedAutomation invite you to visit us at the SG Paris 2014 at the booth of EBDS (European Business Development Services) i4 and see our standard-based solutions for smart grids:

  • com.tom data manager with an integrated service router, switching functionality, various modems, and live data connection to the com.tom internet portal system.
  • IEC 61850, IEC 61400-25, IEC 60870-5-104, and IEC 62351 (security) are integrated to easily build gateways and manage your data.
  • Everything you are looking for - integrated in a single device!
  • Applications: Data Concentrator, System Monitoring, Asset Monitoring, Gateway, RTU, Interface to any process level devices, sensors and actuators, …
  • Examples of applications:

Access to the exhibition is free.

More about com.tom under www.com-tom.de
More about the fair under www.sgparis.fr

See you there.

Thursday, May 22, 2014

VHPReady Website online

Das Industrieforum VHPready e.V. setzt sich für die Realisierung der Energiewende durch die standardisierte Vernetzung dezentraler Energieanlagen ein. Das Industrieforum VHPready e.V. leistet einen Beitrag zur Integration erneuerbarer Energien in den Energiemarkt und ermöglicht den Ausgleich ihrer Volatilitäten durch das orchestrierte Zusammenwirken dezentraler Energieanlagen. Der Standard VHPready und seine Zertifizierung gewährleisten das nahtlose, sichere und kostengünstige Zusammenwirken aller steuerbaren Komponenten und deren Kompatibilität und bilden die Grundlage für flexible Aggregationen dezentraler Energieanlagen zu virtuellen Kraftwerken.

Das Industrieforum hat seit einigen Tagen einen eigenen Webauftritt:

http://vhpready.de/

Click HERE for some discussion of the approach.

Thursday, May 15, 2014

IEC 61850-90-2 for the Communication With Control Centers

The Communication With Control Centers (from substations, power generation stations, and other sites) is usually based on IEC 60870-5-101/-104 or DNP3. The new part IEC 61850-90-2 will describe how IEC 61850 can be used for the above needs.

Experts from ERDF, Siemens, Solvay and RTE have published a paper that describes requirements, concepts and practical experiences related to the communication with control centers:

“Substation to control centre communication based on IEC 61850: requirements, concepts and practical experiences” (Cigre 2012)

SUMMARY
”Featuring object-oriented data models and a standardized configuration language, IEC 61850 represents the state-of-the-art communication standard for substation automation systems. On the other hand, the control centres increasingly promote object-oriented data models and standardized interfaces for data exchange based on IEC 61968 / IEC 61970 (CIM – Common Information Model). For the interconnection of substations and control centres the use of generic signal-oriented communication protocols i.e. IEC 60870-5-101/-104 or DNP3 is still current practice. In order to overcome the limitations of those legacy protocols in terms of data conversions, elaborated data exchanges and proprietary configurations and to foster the use of a seamless object-oriented communication, IEC TC57 is extending the current IEC 61850 specification to close the gap between substations and control centres. The paper gives an introduction into the topic, presents the relevant use cases and derived
requirements. Furthermore it discusses communication and modeling aspects in regards of the use case specific requirements. These concepts are evaluated against industrial power system operator needs. Foreseen consequences for standardization and practical realization of projects are identified.”

The report concludes:

“The experience from projects and systems in operation have proven the benefits of IEC 61850 substation to control centre communication.”

Click HERE for the full paper [pdf]

The Canadian Smart Grid Standards Roadmap and IEC 61850

“The Canadian Smart Grid Standards Roadmap” is a remarkable document that focuses on the real needs for the future of Smart Grid Technologies and standards.

It is no surprise that IEC 61850 is a key standard in this roadmap. The roadmap comes with a list of 17 recommendations on what to do in the future. Two of the six recommendations for Transmission and Distribution (T&D) systems refer to IEC 61850:

Recommendation T&D3:
To support Smart Grid interoperability requirements, the CNC/IEC should encourage the
adoption and application of IEC 61850 for the purpose of communications between
substations
, between substations and control centre, and for transferring synchrophasor data.

Recommendation T&D4:
The CNC/IEC should encourage the development of guidelines and standards for utilities to
migrate from existing, commonly used technologies, to the architecture described in IEC
61850. At the same time, the CNC/IEC should recognize that the large, existing investment
by utilities in the older technologies will require gateway solutions and protocol converters
during the initial transition period.
• In addition, the CNC/IEC should encourage extending this standard to distribution
automation equipment and distributed energy resources
.

Other IEC TC 57 Standards are listed as well: IEC 62357, IEC 61970 and 61968 (CIM), IEC 62351 (Security), as well as IEEE 1815 (DNP3).

Click HERE for the full Roadmap [pdf, 0.9 MB].

Tuesday, May 13, 2014

Want to see IEC 61850 in action? Attend the next Free Workshop

Beck IPC offers two Free of Charge Workshops end of May 2014 in German and in English.

The interest in applying IEC 60870-5-104, DNP3, IEC 61850, IEC 61400-25 … using products of Beck IPC is growing skyrocketing!

The third free of charge Workshop in German is scheduled for:

Datum: 27. Mai 2014
Ort: Wetzlar, etwa 70 km nördlich von Frankfurt
Zeit: 10:00 Uhr - 17:00 Uhr
Programm und Anmeldung (Deutsch).

the second free of charge Workshop in English is scheduled for:

Date: 28. May 2014
Location: Wetzlar (Germany), some 70 km north of Frankfurt
Time: 10:00 h - 17:00 h
Program and registration (English).

Registration information for both events can be found under the above links.

Karlheinz Schwarz (NettedAutomation GmbH) will conduct the workshop. You will learn a lot about the Standards and the many possibilities to apply the various com.tom platforms.

The attendees of the former workshops have appreciated the deep inside view in the standards and how they can be used.

See you there.

Process Data exchange – IEC 61850, DNP3, IEC 60870-5-104, and Portal Solution

The discussion about communication mechanisms and how to get access to the most crucial information is going on. It seems to be clear that there are different requirements for different applications that need to exchange information with a specific IED (at any hierarchy level). There is not a single size that fits all. Modern IEDs will support multiple protocols to support various needs.

One mechanism is using a cloud server – often called a Portal. A simple and beautiful solution is provided by the com.tom (communication to machines) IEDs offered by Beck IPC:

image

See: http://com-tom.de/about.php 

The com.tom IEDs are supporting multiple protocols like IEC 61850, IEC 60870-5-104, Modbus, DNP3, … and a Portal. See the following figure for some details (it shows the web browser connected to the web server at the com.tom):

image

The Input and Output signals (including those configured with IEC 61850!!) will automatically be made available at the Portal as soon as the com.tom is online (trough a router: by Ethernet, WiFi, GPRS, UMTS, …):

image

The Logical Device “PQSrvLDPQ” is visible in the Web Browser (first figure), on the Portal (second figure), in the IEDScout (see next figure), and in IEC 60870-5-104 (last figure):

image

The values are also accessible through IEC 60870-5-104 through a binding of the process values (coming trough Modbus) to 104 messages (configured by the WEB PLC on the com.tom):

image

The different possibilities serve various needs.

It is quite interesting to see such a simple IED supporting these many possibilities – even supporting security (openVPN, firewall, …).

More to come.