Please note that Table A.2 – Definition of mode and behaviour in IEC 61850-7-4 Edition 2 has an error that has been corrected, see Tissue 671:
For incoming data with q.test = True and Mode on, the data shall be processed as invalid!
Access IEC 61850-7-4 Tissue 671.