Wednesday, September 23, 2026

Update on Traffic Engineering with IEC 61850

The other day I have discussed Traffic Engineering with IEC 61850. In a second post today I showed how SCL can be used to validate incoming messages.

Now I will show you in the analogy of traffic control how limits on the street are signaled. Fotos by Karlheinz Schwarz. 

First example Maximum Load Limit on a bridge: 


Second example with three limits: one vehicle at a time, max gross weight, and max speed:


Third example: max Tunnel hight 4,00 Meter

I guess you understand that IEC 61850 SCL can be used to configure signals for limits ... 

Enjoy. 

Cyberattacks Targeting OT Systems and IEC 61850

According to Security Week, "Hackers targeted operational technology (OT) systems at two private water utilities in Colorado in late August, apparently attempting to cause disruptions.

Few technical details are available, but it seems the attackers targeted industrial control systems (ICS) at the water utilities, which serve fewer than 200 people. 

A spokesperson for Colorado Governor Jared Polis told The Denver Post [paywalled] that the attackers changed equipment settings, disabled remote access and alarms, and altered pumping cycles. However, the disruptions were brief and did not affect water services or public safety."

I highly recommend small and all electric power utilities to pay attention to this situation and improve the cyber-security of the power system devices like SCADA, control, protection, RTUs, ... changing equipment settings could cause dangerous situations like blackouts, ... 

IEC 61850 information models can play an important role when somebody wants to change settings of a process control signal. The other day I used the IEDScout from Omicron to limit the setting value of a CDC=APC (Analogue Setting) structured setting. I set the maxVal to 1,000 (in the server) and tried with a second instance of IEDScout as a client to set the process value to Oper.ctlVal > maxVal ... the server responds with an MMS Write-Error and a Report "Inconsistent-parameters". The server did not accept a value outside of the maxVal and minVal. The process value did not change at all!

This possibility is a standardized (kind of "security") function incorporated into the CDC=APC !!!

Sure, the maxVal and minVal should be blocked for online changes! That could be configured in the CSL file as well.

So, IEC 61850 and especially SCL provide more than just a communication configuration ... many function related definitions are defined for the various common data classes!!

Let me know in case you want to further discuss this.

P.S.: After I published the above post I came across the following LinkedIn post   

CVE-2025-6625 — Improper Input Validation
> Crafted FTP command can take the controller offline
> CVSS 7.5 — network reachable, no auth, availability hit
> Energy, water, manufacturing fleets still run these PACs

Input VALIDATION is a crucial issue ... YES!

P.S2.: I just read another post on LinkedIn regarding DNP3 message validation. Interesting.

P.S3: Update

Monday, August 17, 2026

IEC 61850 for Newbees - Traffic Engineering with IEC 61850-6 (SCL)

I agree: The standard series IEC 61850 is quite comprehensive ... some believe it is complex. Ok. What can I do to help you getting a better understanding? I will try to help you. 

Today I will show how IEC 61850-6 (SCL, System Configuration Language) can be used for traffic engineering - traffic means: "signals" are communicated back an forth: analogue measurements, status measurements, control, configuration, event-driven reports, event-driven logs, ... start and stop of event recorder, trip-signals, ... in IEC 61850 "signals" are named and a binding of an instance to the application process (e.g., Bay1 Circuit Breaker 2) is specified ...

I am using a brief prose language ... this description could be transformed to an SCL compliant (machine processable ) XML file.

The many "signals" are travelling from a source to a destination ... let's say the following valid (allowed) routes are:

  1. A->B,
  2. B->A,
  3. V->A,
  4. A->C, 
  5. D->E, 
  6. R->S, 
  7. R->A

Each letter is representing a source or destination of the "signal" flow. The "->" is representing one of the specific "signals" standardized in IEC 61850. In the first route A sends an operate to B and B is reporting back to A a changed status information ...

In SCL we can configure now for each route in detail the sources, destinations, strongly typed "signals", communication services, ... The SCL compliant System Configuration Description (SCD) would list all details on all routes ... 

The source knows by the SCD document which "signal" is to be sent (when and how) to which destination. The destination knows by the SCD document which "signal" it receives (from which device, when and how).

What else can we do with the SCD file?

  1. A tool could check if all source and destination (devices) are specified ... a source A is configured to send a signal to B ... Is B at all specified? Maybe it was forgotten.
  2. A tool could check if for all source and destination devices the addresses are configured. 
  3. Another tool could check if all traveling "signals" (messages) are specified in the SCD document. A "signal" that travels during online operation from X to B (here X tries to connect to B) is not specified and thus NOT ALOWED. The tool could rase the red flag telling the system engineer that an unknown device X is active on the network. 
  4. ... many other possibilities are listed in the following figures from my seminar slides (some 10+) years old.


I hope you got an impression what IEC 61850-6 (SCL) could provide.
SCL is the backbone of IEC 61850!
Check HERE for a crucial use-case for SCL (cyber security ...).
Let me know if you have a question on this post.
P.S: Update

Monday, May 7, 2012

Draft IEC 61850-90-4 – Network engineering guidelines

IEC has published the following draft for ballot (57/1238/DTR):

IEC 61850-90-4 TR Ed.1:
Communication networks and systems for power utility automation –
Part 90-4: Network engineering guidelines for substations

The ballot closes on 2012-06-22.

Please contact your national committee to get a copy of this crucial document.

This 192 page Technical Report provides definitions, guidelines, and specifications for the network engineering of IEC 61850 based (substation and other) automation.
It addresses issues such as Ethernet technology, network topology, redundancy, traffic latency and quality of service, traffic management by multicast and VLAN, network-based clock synchronization and testing of the network.