Showing posts with label IEC 61850-7-510. Show all posts
Showing posts with label IEC 61850-7-510. Show all posts

Tuesday, August 7, 2012

IEC 61850-7-410 Edition 2 is out for ballot

IEC 61850-7-410 Edition 2:
Communication networks and systems for power utility automation –
Part 7-410: Basic communication structure – Hydroelectric power plants –
Communication for monitoring and control

has been published for final ballot until 2012-10-05.

Changes in Edition 2 :

  • Generic logical nodes in IEC 61850-7-410 Edition 1 that are not specific to hydropower plants have been moved to IEC 61850-7-4 Edition 2.
  • The definitions of logical nodes have been cleaned up.
  • Most of the modeling examples and background information has been moved to IEC/TR 61850-7-510 Edition 1 (see example below).
  • New general-purpose logical nodes that are not included in IEC 61850-7-4 Edition 2, have been defined.

IEC 61850-7-410 Edition 2 defines 46 Logical Node classes and several hundred data objects:

LN Class Description
ACTM Control mode selection.
AJCL Joint control function, to balance total power from different sources.
APSS PSS Control. Common information of a PSS function.
APST PSS 2A/B filter. Represents a filter according to IEEE 421.5-2005.
APSF PSS 4B filter. Represents a filter according to IEEE 421.5-2005.
FHBT Heart beat function of a controlling device.
FSCH Scheduler. This LN represents a task scheduler
FXPS Functional priority status.
HBRG Turbine – generator shaft bearing.
HCOM Combinator (3D CAM or 2D CAM)
HDAM Hydropower dam.
HDFL Deflector control.
HDLS Dam leakage supervision.
HEBR Electrical brake.
HGPI Gate position indicator.
HGOV Governor control.
HGTE Dam gate.
HITG Intake gate.
HJCL Power plant joint control function.
HLKG Leakage supervision.
HLVL Water level indicator.
HMBR Mechanical brake for the generator shaft.
HNDL Needle control.
HNHD Net head data.
HOTP Dam overtopping protection.
HRES Water reservoir.
HSEQ Start / stop sequencer.
HSPD Speed monitoring.
HSST Surge shaft or surge tank.
HTGV Guide vanes (wicket gate).
HTRB Runner blades.
HTRK Trash rack,
HTUR Turbine.
HUNT Hydropower production unit.
HVLV Valve.
HWCL Water control function.
IFIR Generic fire detection and alarm function.
IHND Generic physical human – machine interface.
KHTR Heater.
PRTR Rotor protection.
RFBC Field breaker configuration.
SFLW Media flow supervision.
SLEV Media level supervision.
SPOS Device position supervision.
SPRS Media pressure supervision.
XFFL Field flashing.

Voltage regulation example from IEC TR 61850-7-510 Ed1:

image

This figure shows the relation between an application function and the IEC 61850 object models.

IEC TR 61850-7-510 Ed1 (86 pages) is a comprehensive guide “how to use IEC 61850 for hydro power plants”.

Preview of IEC TR 61850-7-510 Ed1

Friday, June 15, 2012

IEC 61850-90-13 – New Work on IEC 61850 for Steam and Gas Turbines

The new work item has been introduced in the work programme under the title:
IEC 61850-90-13 Ed.1 (57/1259/RVN):
Communication networks and systems for power utility automation –
Part 90-13: Extension of IEC 61850 information models to also include logical nodes and data models for steam and gas turbines

IEC 61850 defines very common concepts, information models, services and configuration language that can be used in many other application domains outside substations. MMS – as a basic communication service to which IEC 61850 models and services are mapped – was originally defined for the manufacturing floor (MMS – Manufacturing Message Specification). So it is no surprise that it can be used there and in many other application domains.

One key issue in power plants is the RDS PP (related to KKS):

 image

Examples of RDS PP for Wind Power Plants and IEC 61400-25/61850:

image

Binding of Information Models:

image 

image

Examples from IEC 61850-7-510 (Hydroelectric power plants – Modelling concepts and guidelines):

image

image

Step by step we learn that IEC 61850 is in harmony with many other designation standards … and it can be used for almost all online (runtime) information exchange and system and IED configuration.