Showing posts with label reactive power control. Show all posts
Showing posts with label reactive power control. Show all posts

Friday, August 31, 2012

Details of Inverter-based DER Devices Modelled in IEC 61850-90-7

Functions and Information Exchanges for Inverter-based DER Devices are modeled in IEC 61850-90-7. What does this document provide? A lot of useful models for real functions needed (today and in the near future) in power distribution systems with massive renewable power fed into the grid. The main models can be found in a document published the other day (see link below).

You can find many functions described and modeled in IEC 61850-90-7, e.g., frequency-watt mode:

image

This frequency-watt mode addresses the issue that high frequency often is a sign of too much power in the grid, and vice versa. These extreme deviations from nominal frequency can cause grid instability, particularly if they cause significant amounts of generating equipment to trip off-line.
One method for countering this over-power problem is to reduce power in response to rising frequency (and vice versa if storage is available). Adding hysteresis provides additional flexibility for determining the active power as frequency returns toward nominal.

The IEC 61850-90-7 has been written to meet crucial needs in the power delivery system. This document has to be seen in conjunction with other standards as depicted in the UML diagram below:

image 

The electrical measurements like voltage, current and frequency are defined in IEC 61850-7-4 Ed2.

Note that the conversion of almost all models into UML (Enterprise Architect) will be completed soon. The huge model will be used to maintain the models in future. This is a crucial step toward tool based standardization.

Download the models based on IEC 61850-90-7 [pdf, 1.1 MB]

Tuesday, November 17, 2009

Active and Reactive Power Control with IEC 61400-25-2

The focus of the IEC 61400-25 series is on the communications between wind power plant components such as wind turbines and actors such as SCADA systems. IEC 61400-25-2 specifies the information model of devices and functions related to wind power plant applications. These models extend IEC 61850-7-x models. Almost all definitions, hardware and software solutions available for IEC 61850 can be used for IEC 61400-25-2. In particular, IEC 61400-25-2 specifies the compatible logical node names, and data names for communication between wind power plant components.

The standard IEC 61400-25-2 defines a comprehensive list of information models (Logical Nodes) for wind turbines, e.g.:

  • WTUR - Wind turbine general information
  • WROT - Wind turbine rotor information
  • WTRM - Wind turbine transmission information
  • WGEN - Wind turbine generator information
  • WCNV - Wind turbine converter information
  • WTRF - Wind turbine transformer information
  • WNAC - Wind turbine nacelle information
  • WYAW - Wind turbine yawing information
  • WTOW - Wind turbine tower information

The most crucial Logical Nodes are likely the

  • WAPC - Wind power plant active power control information
  • WRPC - Wind power plant reactive power control information

These models describe the "interface" between a complete park and the grid operator for control purposes. These Logical Nodes can be used for other power resources like CHP, PV, ... The German EEG (Erneuerbare-Energien-Gesetz) accelerates the application of IEC 61400-25 tremendously, because the Grid Operator needs more information about the park and he needs to control the whole power system in cases of faults and critical conditions - wind power plants and other resources are an integrated part of the whole system. These resources cannot be treated just as negative loads.

The WAPC (active power control) comprises the following Data Objects:

Status information

  • Actual number of wind turbines in operation
  • Active Power Limitation Mode Enabled
  • Active Power Control Mode Enabled controlling apparent power
  • Gradient Function Enabled
  • Delta Function Enabled

Measurements

  • Wind Power Plant active power output capability
  • Wind Power Plant active power output
  • Wind Power Plant apparent power
  • Wind Power Plant Gradient
  • Wind Power Plant active power reserve utilizing the Delta function –
    the difference between active power generation capability and active
    power generated

Control information

  • Activate active power control function
  • Activate apparent power control function
  • Activate gradient control function
  • Activate delta control function
  • Set reference value for the wind power plant active power output
  • Set reference value for the wind power plant apparent power output
  • Set reference value for gradient ramping up the wind power plant active power output
  • Set reference value for gradient ramping down the wind power plant
    active power output
  • Set reference value for the wind power plant active power reserve –
    also named as “spinning reserve”

The information provided by these models is crucial for a future stable power delivery system.