Showing posts with label publisher. Show all posts
Showing posts with label publisher. Show all posts

Tuesday, February 27, 2024

What is an IED (Intelligent Electronic Device)?

IEC 61850 deals a lot with IEDs. But: What is an IED?

First you can check with two documents of the series IEC 61850:

IEC 61850-1 - Intelligent Electronic Device (IED)
any device incorporating one or more processors with the capability of receiving or sending data/control from or to an external source (for example, electronic multifunktional meters, digital relays, controllers)

IEC 61850-1 - Physical Device (PD)
equivalent to an IED as used in the context of this standard

IEC 61850-5 - Intelligent electronic device (IED)
device incorporating one or more processors with the capability to execute application 
functions, store data locally in a memory and exchange data with other IEDs (sources or sinks) over a digital link

Many years after these definitions have been published, we have different views on the term IED:
Physical IED (in the context of IEC 61850 and IEC 61400-25) - any physical device incorporating one or more processors with the capability of exchanging information (derived from IEC 61850 information models and exchanged with IEC 61850 services for client/server and publisher/subscriber) with other physical device(s). The semantic, the coding and decoding of the exchanged information (messages) follows the standard series.
IED Configuration (in the context of IEC 61850 and IEC 61400-25) - formal description (section in the SCL according to part 6) of the IEC 61850 information models linked to the IEC 61850 information exchange roles client, server, publisher, or subscriber, and the signal flow between physical IEDs.
IED Role (in the context of IEC 61850 and IEC 61400-25) - implementation of the IED Configuration: implementation of the IEC 61850 information model plus implementation of any combination of the following information exchange roles: client, server, publisher, or subscriber.
A Physical IED can host any combination of IED Roles.
Note: A gateway may host a server role to an up-link (first SCL file plus a client role and a subscriber role (both configured in a second SCL file) to the underlying Physical IEDs.
Please note that in SCL a Server configuration comprises the models including the DataSets, Report Control Blocks, GOOSE Control Blocks, SV Control Blocks, and Log Control Blocks:







From a communication point of view GOOSE and SV publisher and subscriber are NOT part of the client/server communication ... 
I hope this definition will help to reduce the disconnects in the communication of the experts.
Let me know what you think.

Monday, July 3, 2017

An All NEW Evaluation, Demo, Hands-On Package for IEC 61850 and IEC 61400-25

NettedAutomation GmbH (Karlsruhe, Germany) has released an All NEW Evaluation, Demo, Hands-On Package for IEC 61850 and IEC 61400-25 (EvaDeHon) for immediate download and use!
The new EvaDeHon Package comprises the roles Client, Server, Publisher, and Subscriber running on a PC, HMS (IXXAT, Beck IPC) Gateways, SystemCorp IEDs, ...
The new solutions allow to run multiple IED models (all roles) in parallel on one PC (simulating IEDs of a complete system!) ... and more. The roles and applications are configured directly by SCL files (.cid). You can build your own models and run them with all roles ... if configured.
This Package is based on our 30+ years of experience. We are really proud of offering these tools to the industry today! Sit down, enjoy and relax ...


Copyright, 2017, Michael Hüter

Click HERE to download the documentation only [pdf, 3.2 MB]
Click HERE for downloading the demo package including the documentation and license conditions.

Example: Server and Client on two PCs:


Many topologies on PCs:


... and topologies with gateways:


Click HERE to download the documentation only [pdf, 3.2 MB]
Click HERE for downloading the demo package including the documentation and license conditions.


Wednesday, April 26, 2017

NEW IEC 61850 Demo Package for Windows available

The main purpose of the new demonstration and evaluation package is to provide a free of charge simple and easy to use IEC 61850 Client/Subscriber Tool (running on Windows PCs) that can be used to communicate with a Server/Publisher implemented on the platforms:

Beck IPC DK151 Development Kit for SC145 (DK61)
Beck IPC com.tom / IXXAT SG-gateways (WEB-PLC)
SystemCorp Smart Grid Controllers
Windows PC

Several other uses cases are possible:

The demonstration uses a single generic SCL model (and a derived JSON file [JavaScript Object Notation] that can (beyond the main purpose) be used on the above platforms to automatically configure (tree structured graphical applications) for Clients, Server/Publisher, and Client/Subscriber roles as shown on the next slides.

The specification of additional models (.icd and .json) could be provided for a fee. 
Contact NettedAutomation if you are looking for other models, please.
Click HERE for further details and instructions to download the new package including the documentation.
Click HERE for documentation only.
The package is used in our training courses.